Case study · Networked lighting controls
Stairwells that never go dark
64 units in Upper Manhattan — two stairwells, eight corridor floors and the common rooms, already LED, every fixture at full around the clock.
Multifamily · Upper Manhattan · 13 zones
Schedule
Zone by zone
Thirteen zones: two stairs, eight corridor floors, and the common rooms.
| Zone | Space | Hrs/yr | Control | Why |
|---|---|---|---|---|
| Z-1 – Z-2 | Stairwells ×2 | 8,760 | 20% bi-level, lift a flight ahead | Egress light can never go dark |
| Z-3 – Z-10 | Corridors, one per floor | 8,760 | 20% standby, occupancy to full | Occupied minutes at a time |
| Z-11 | Lobby and mail | 8,760 | Daylight + occupancy, trimmed | Glazed front; daylit mornings |
| Z-12 – Z-13 | Laundry and bike room | 5,000 | Occupancy, full off | No standby needed behind doors |
Commissioned
Sequence of operations
How each zone is programmed.
| Space | Sequence | Note |
|---|---|---|
| Stairwells ×2 | 20% standby · lift a flight ahead | Bi-level egress, never dark |
| Corridors ×8 | 20% standby · occupancy to full | One floor lifts at a time |
| All fixtures | high-end trim at 85% | Tuned to the space, not the spec sheet |
| Common rooms | occupancy · full off behind doors | Laundry doesn't idle lit |
Calculated
Annual impact
14,480kWh avoided / yr
$3,620saved / yr at $0.25/kWh
5.7 t
CO₂ avoided / yr
≈640
gallons of gasoline equivalent
≈95
tree seedlings grown 10 years